Installation Premier 412/816/832 Installation Manual
16 INS159-13
Single EOL - N/C & N/O (Burglary)
Use this wiring configuration when connecting a mixture of normally
closed and normally open detection devices to the zone. Ensure
that the zone is programmed for Single EOL - N/C & N/O operation
(see page 27). The zone must be wired as follows:
Single EOL - N/O (Fire)
Use this wiring configuration when connecting a 4-wire smoke
detector to the zone. Ensure that the zone is programmed for Single
EOL - N/O (Fire) operation (see page 27). The zone must be wired
as follows:
Single EOL - N/C
Use this wiring configuration when connecting just normally
closed detection devices to the zone. Ensure that the zone
is programmed for Single EOL - N/C operation (see page
27). The zone must be wired as follows:
Single EOL - O/C Tamper
Use this wiring configuration when connecting just normally closed
detection devices to a zone and when a tamper response is
required in the event of an open circuit. Ensure that the zone is
programmed for Single EOL - O/C Tamper operation (see page 27).
The zone must be wired as follows:
Single EOL S/C Tamper
Use this wiring configuration when connecting just normally closed
detection devices to the zone and when a tamper response is
required in the event of a short circuit. Ensure that the zone is
programmed for Single EOL - S/C Tamper operation (see page 27).
Wire Single EOL - S/C Tamper zones as shown for Single EOL -
N/C.