Premier 412/816/832 Installation Manual Programming the Control Panel
INS159-13 37
Panel NVM is Locked
On: The NVM is locked and the “Load Defaults” jumper pins on
the main PCB are disabled, thus preventing the factory
defaults from being loaded.
Off: The “Load Defaults” jumper pins on the main PCB are
enabled, thus allowing the panel to be defaulted.
Power Savings during AC Mains Failure
On: The back-lighting for all remote keypads is switched off
during a mains failure.
Off: The back-lighting is enabled during a mains failure.
Line Fault Overrides Bell Delay
On: The system will override the bell delay in the event of a
telephone line fault.
Off: The system will enforce the bell delay.
Two-Wire Smoke Detection on O/P 1
On: Panel Output 1 is enabled for 2-wire smoke detectors (JP1 on
the main PCB must also be removed, see page 8).
Off: Panel Output is a normal programmable output.
Convert Siren O/P from Voltage to Speaker Driver
On: The Siren output terminals on the main PCB are configured
for a speaker driver.
Off: The Siren output terminals on the main PCB are configured
for Voltage output to power a bell or siren.
System Options 2
The function of each option is described as follows:
Tamper Alarms Cause a Trouble While Disarmed
On: Tamper alarms cause a trouble condition while the system is
disarmed.
Off: Tamper alarms cause an alarm while the system is disarmed.
Tamper Alarms Cause a Trouble While Stay Armed
On: Tamper alarms cause a trouble condition while the system is
Stay armed.
Off: Tamper alarms cause an alarm while the system is Stay
armed.
Defer Reporting of Non-Zone Restorals
On: The communicator reporting of non-zone restorals will be
deferred until the Restore Reporting Delay timer expires or
until the system is disarmed (see 4 below).
Off: Non-zone restorals will report immediately as they occur.
Use Delay Timer to Defer Non-Zone Restorals
On: If System Option 2.3 (see above) is enabled, then enabling
this option will defer the non-zone restoral reporting until the
Restore Reporting Delay Timer has elapsed.
Off: Non-zone restorals are deferred until the system is disarmed.
Inhibit Keyswitch Operation upon EOL Tamper
On: Tampering of a keyswitch zone will inhibit the keyswitch
operation.
Off: Tampering will not inhibit the keyswitch operation.
Away Arm Overrides Alarm Transmission Delay
On: The ‘Alarm Transmission Delay’ timer is overridden when the
system/partition is away armed.
Off: The ‘Alarm Transmission Delay’ timer is not overridden.
Defer Reporting of Zone Restorals
On: The communicator reporting of zone restorals will be deferred
until the Restore Reporting Delay Timer expires or until the
system is disarmed (see 8 below).
Off: Zone restorals will report immediately as they occur.
Use Delay Timer to Defer Zone Restorals
On: If System Option 2.7 (see above) is enabled, then enabling
this option will defer the zone restoral reporting until the
Restore Reporting Delay Timer has elapsed.
Off: Zone restorals are deferred until the system is disarmed.
System Options 3
The function of each option is described as follows:
Away Arm Exit Error Doesn’t Sound Bell
On: The bells will not sound if an exit error occurs when the
system is away armed.
Off: The system will sound the bell if an exit error occurs when the
system is away armed.
Zone Test - Silence on No Violation
On: The Zone Test sounder is silent when all zones are secure
and will pulse sound when one or more zones are violated.
Off: The Zone Test sounder is on continuously when all zones are
secure and will pulse sound when one or more zones are
violated.
Alarm Status Light Indicates Fire
On: The alarm status light will only indicate Fire alarms. Fire
alarms activated from zones will illuminate the relevant zone
light and the alarm light. Fire alarms activated from a 2-wire
smoke detector will only illuminate the alarm light. All other
zone alarms will illuminate the relevant zone light only.
Off: The alarm status light indicates both alarms and fire alarms.
Enable Entry/Exit Tones for Panel Speaker
On: The panel speaker will produce entry/exit tones.
Off: The panel speaker only produces alarm and trouble tones.
Enable Cross Partitioning
On: The user may temporarily switch to another partition by
pressing the key, and the relevant partition number.
Once the remote keypad has been selected for another
partition, the indicator lights will only display information
relevant for the selected partition. The remote keypad will
revert back to its normal partition 15 seconds after the last
key press or 1 minute after the last entry of a User code.
Off: All remote keypads are locked to their programmed partition
number and the user cannot switch to another partition.
Enable EN 50131-1 Requirements
On: The Engineer code will only be accepted if the user has
authorised Remote/Engineer Access (see page 69). If an
alarm occurs during entry (timed-out entry alarm) the system
will generate an internal alarm for 30 seconds before
activating the bell and communicator. Wireless detectors
must have polled in within 20 minutes when attempting to
arm the system. Mag 2 input on the RadioPlus magnetic
contact is a tamper input.
Off: The Engineer code is accepted at all times and the timed-out
entry alarms respond as normal. Wireless detectors do not
need to poll in within 20 minutes when attempting to arm the
system. Mag 2 input on the RadioPlus magnetic contact is an
alarm input.
Reinstate Bypassed Zones on Disarm
On: Any zones that have been manually bypassed are
automatically reinstated when the partition is disarmed.
Off: Any zones that have been manually bypassed will remain
bypassed when the partition is disarmed.
Invert Panel Siren Output
On: When the panel siren output is configured for voltage drive
(see System Options 1.8 on page 37) the output is inverted,
i.e. Bells off = voltage applied, Bells on = voltage removed.