Commissioning & Troubleshooting Premier 412/816/832 Installation Manual
20 INS159-13
3. Commissioning & Troubleshooting
Commissioning
Once ALL connections have been made to the control panel and
power is ready to be applied, you should read this section before
continuing.
The control panel leaves the factory with default settings. For a
complete list of factory default settings, please refer to the
programming worksheets from page 86.
Connect the black battery lead to the negative () terminal of
the standby battery and the red battery lead to the positive (+)
terminal of the standby battery. The green power light on the
main PCB will flash whilst the default values are being loaded.
If the system has gone into an alarm condition, enter the
default Master User code . The alarm tone
will then stop.
To access the Engineer Programming Menu, enter the default
Engineer code  and press followed
by . All the zone lights will illuminate.
Panels with V16 or later firmware installed will use the start-up
procedure found on page 23
Confirm Devices see page 22
Program the system date and time, see page 69.
Select the Language, see page 36.
Select the Country Code, see page 36.
Program the system as described in the next section
(Programming the Control Panel).
Perform a walk test as described on page 69. Remember that
some powered detectors (e.g. PIRs and combined technology
detectors) take several minutes to warm up and become
operational.
Test the internal sounder, external sounder and strobe as
described on page 69.
Replace the lid and secure with the two lid screws supplied -
do not over-tighten.
Replace the screw covers.
Press to leave the programming menus. All the zone
lights will turn off.
The Service light will be flashing to indicate that action is
required. Switch on the mains supply to the control panel. The
Service light will stop flashing and stay on continuously.
Installation is now complete and the system is
ready for use.
Troubleshooting
Power Faults
No Power to Unit (mains only)
Check the mains block fuse and replace if blown.
Check for any loose wires at the mains block, the transformer
and the AC terminals on the PCB.
Check the mains block is connected correctly; live to live
(brown), neutral to neutral (blue).
No Power to Unit (battery only)
Make sure the “Kick Start” pins have been shorted together.
Check for any loose wires at the BATT terminals on the PCB.
Check that the battery wires are connected correctly; red from
BATT+ to the battery positive [+], black from BATT- to the
battery negative [].
Remote Keypads
Keypad Does Not Operate at All
Check that the remote keypad is wired correctly from the
control panel.
Check that the network fault indicator is off. If the indicator is
on, the electronic fuse has activated indicating a short circuit
across the [+] and [] of the network terminals.
Keypad Does Not Accept Access Codes
If the system has more than one remote keypad check that
each keypad is addressed differently, see page 12 for details.
The address of a keypad can be checked by pressing the
and keys together, the address is displayed by the
relevant zone light.
Check that the remote keypad is wired correctly.
If the remote keypad is on a cable run that is longer than 100m,
check the voltage between the [+] and [] terminals at the
remote and ensure that it measures no less than 10.0V.
Check that you are using the correct Access code. The default
Engineer code is  and the default Master
User code is .
Check that the User code you are using is not “Time Locked”,
if the User code is time locked then the Access code will only
be accepted when Control Timer 1 is off, see page 66 for
further details.
Keypad Does Not Generate Alarm Tones etc.
Each keypad can be configured so that the alarm, entry, exit,
chime tones etc. can be enabled or disabled. Check that the
keypad has been programmed correctly, see page 42 for
details.
Keypad Emergency Keys Do Not Operate
Each keypad can be configured so that the emergency keys
FIRE, POLICE and MEDICAL can be enabled or disabled.
Check that the keypad has been programmed correctly, see
page 42 for details.
Remote Expander
Expander Does Not Operate at All
Check that the expander is wired correctly from the control
panel.
Check that the network fault indicator is off. If the indicator is
on, the electronic fuse has activated indicating a short circuit
across the [+] and [] of the network terminals.
System Does Not Recognise Zones 9 to 16
If the expander is on a cable run that is longer than 100m,
check the voltage between the [+] and [] terminals at the
remote and ensure that it measures no less than 10.0V.