Premier 412/816/832 Installation Manual Specifications
INS159-13 79
Current Consumption
Nominal (model dependant):
When fully back lit:
Zone Indicators
Premier RKP4/8/16:
Premier RKP8/16 Plus:
Premier LCD/LCDL/FMK/SMK:
LED (4/8/16)
LED (8/16)
32 Character (Standard/Large)
-10C to +55C
+14F to +131F
Residential/Commercial/Light Industrial
or Industrial
Dimensions:
Premier RKP4/8/16
Premier RKP8/16 Plus/LCD/-L/P
140mm x 105mm x 35mm
145mm x 115mm x 30mm
Current Consumption
Nominal:
In Alarm with Speaker:
Zones
Number:
EOL Resistor Value:
-10C to +55C
+14F to +131F
Residential/Commercial/Light
Industrial or Industrial
Zones
Number:
EOL Resistor Value:
-10C to +55C
+14F to +131F
Residential/Commercial/Light
Industrial or Industrial
Safety Notes
1. Only use batteries of the specified type.
2. Dispose of used batteries safely according to the
manufacturer's instructions.
3. Locate the battery inside the panel space provided.
4. This equipment is designed for dry indoor use only.
5. When replacing a fuse always observe the specified rating and
type - failure to do so is dangerous and will invalidate the
warranty. Fuses should comply with IEC 127.
6. The press-seal bag must not be stored inside the panel.
Standards
Texecom declares that this product complies with
the requirements of the following directives:
2004/108/EC EMC Directive
2006/95/EC LVD Directive
2011/65/EU RoHS Directive
The product therefore meets all the requirements
to enable it to be CE marked.
Weee Directive: 2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon the purchase
of equivalent new equipment, or dispose of it at
designated collection points. For more information
see: www.recyclethis.info.
This product is suitable for use in systems designed to comply
with EN 50131-1 at grade 2 and environmental class II.
EN 50131-1/3/6 Compliance
In order to comply with the requirements of EN 50131-1, EN 50131-
3 and EN 50131-6 the following programming and system
configuration must be implemented:
Menu Options 39 1-8 must all be turned ON, see page 40.
EN 50131-1 Requirements must be programmed as “Enabled”,
see page 37.
The “Permanent Keypad Status Display” option must be
programmed to “Disabled” for all remote keypads, see page
42. In addition the “Courtesy Delay” timer must not be set
above 180 seconds, see page 36.
The “Partition Entry Delay” timers must not be programmed
above 45 seconds, see page 31.
The “Partition Bell Delay” timers must not be programmed
above 10 minutes, see page 31.
The “Partition Bell Duration” timers must be programmed
between 2 and 15 minutes, see page 31.
“Quick Arm”, “Quick Disarm” and “Quick Bypass” option must
be programmed to “Disabled” for all remote keypads, see
page 42.
The “Tamper Alarms Cause a Trouble While Disarmed” option
must be “Enabled”, see page 37.
Do not fit more than 10 unpowered detectors per zone.
Do not fit more than one non-latching powered detector per
zone.
Do not mix unpowered detectors and non-latching detectors
on a zone.
A Type W must not be used.