EasyManua.ls Logo

TEXIO PDS20-10A - Local Bus Connection

TEXIO PDS20-10A
117 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82
82
The PC address is used to identify the device when DHCP or Auto IP is selected. When the IP address is a
fixed IP, there is no need to configure the PC address.
For details about configuring an automatic IP address or COM redirector, see the corresponding section in the
operation manual. You can download the operation manual from our company's website.
11-1-11. Local bus connection
In a local bus connection, the master PDS-A power supply unit used to communicate with the PC can control up to 30
slave PDS-A power supply units connected (in cascade arrangement) to the master unit via a dedicated modular
cable.
The use of RS-485 signals in a local bus connection makes it possible to extend the distance between devices.
However, in order to ensure stable control, the lengths of the cables used should be kept as short as possible.
PC
PDS-A power supply
(Slave unit)
System address : 2
Terminating resistor
: OFF
PDS-A power supply
(Master unit)
System address : 1
Terminating resistor: ON
GP-IBUSB RS-232C or LAN
PDS-A power supply
(Slave unit)
System address : 3
Terminating resistor
: OFF
PDS-A power supply
(Slave unit)
System address : 4
Terminating resistor: ON
Local bus Local bus Local bus
When specifying slave units, use the ADRS command to specify the system address number.
For the interface setting of the slave unit IF-70GU, the available values are USB or GP-IB.
An IF-70RS configured for RS-232C communication can be used as an interface for slave units.
Only the terminators at each end of the local bus should be on. The other terminators should be off.
In the figure above, the terminators for system addresses 1 and 4 are set to "ON". The rest are set to "OFF".
IF card
Setting
Master unit
Intermediate slave unit
End of slave unit
IF-70GU
System address
1
2 to 31
PC address
0 to 31
Cannot be specified
IF card mode setting
USB or GPIB
Not used. USB or GPIB can be specified.
IF card terminator
ON
OFF
ON
IF-71RS
System address
1
2 to 31
PC address
Cannot be specified
Cannot be specified
IF card mode setting
RS-232C
RS-232C
IF card terminator
ON
OFF
OFF
IF-71LU
System address
1
2 to 31
PC address
0 to 31
Cannot be specified
IF card mode setting
USB or LAN
Not used. USB or LAN can be specified.
IF card terminator
ON
OFF
ON

Table of Contents