GX9 ASD Installation and Operation Manual 99
OUT6 OFF Delay
Program Terminal Output Terminal Delays
This parameter delays the opening of the OUT6 output terminals by the
programmed value (see waveforms at F160).
The delay may be increased to prevent relay chatter.
Direct Access Number — F165
Parameter Type — Numerical
Factory Default 2
Changeable During Run — No
Minimum — 2
Maximum — 200
Units — mS
OUT7 OFF Delay
Program Terminal Output Terminal Delays
This parameter delays the opening of the OUT7 output terminals by the
programmed value (see waveforms at F160).
The delay may be increased to prevent relay chatter.
Direct Access Number — F166
Parameter Type — Numerical
Factory Default 2
Changeable During Run — No
Minimum — 2
Maximum — 200
Units — mS
Base Frequency 2
Program Motor Motor Set 2
The Base Frequency 2 setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The Base Frequency Voltage 2
parameter is set at F171.
This parameter is used only when the parameters for Motor Set 2 are
configured and selected. Motor Set 2 may be selected by a properly configured
input terminal (see Table 8 on pg. 217).
For proper motor operation, the Base Frequency should be set for the
nameplated frequency of the motor.
Direct Access Number — F170
Parameter Type — Numerical
Factory Default 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Base Frequency Voltage 2
Program Motor Motor Set 2
The Base Frequency Voltage 2 setting is the Motor 2 output voltage at the
Base Frequency (F170). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Correction setting (F307).
This parameter is used only when the parameters for Motor Set 2 are
configured and selected. Motor Set 2 may be selected by a properly configured
input terminal (see Table 8 on pg. 217).
Direct Access Number — F171
Parameter Type — Numerical
Factory Default (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 700.0
Units — Volts
Manual Torque Boost 2
Program Motor Motor Set 2
The Manual Torque Boost 2 function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the Base Frequency 2 setting (F170).
See parameter F016 (Manual Torque Boost 1) for an explanation of torque
boost.
This parameter is used only when the parameters for Motor Set 2 are
configured and selected. Motor Set 2 may be selected by a properly configured
input terminal (see Table 8 on pg. 217).
Direct Access Number — F172
Parameter Type — Numerical
Factory Default (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.00
Units — %
F165 F172