GX9 ASD Installation and Operation Manual 103
V/f Five-Point 1 Voltage
Program Special V/f 5-Point Setting
The V/f 5-Point 1 Voltage establishes the output voltage level that is to be
associated with the frequency setting of F190 (V/f 5-Point 1 Frequency).
The F701 parameter setting will determine if the on-screen selection for this
parameter appears in the form of a Voltage (V) or as a Percentage (%) of the
ASD rating.
If using Voltage as a unit of measure and with no voltage correction (F307
Disabled), the limit of the on-screen display value for this parameter is 575.00
Volts.
If using % as a unit of measure and with no voltage correction (F307 Disabled),
the ASD output voltage will be the percentage setting times the ASD rated
voltage.
See F190 for additional information on this setting.
Direct Access Number — F191
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — V or % (F701)
Units — V or % (F701)
V/f Five-Point 2 Frequency
Program Special V/f 5-Point Setting
The V/f 5-Point 2 Frequency sets the frequency to be associated with the
voltage setting of parameter F193 (V/f 5-Point 2 Voltage).
See F190 and F191 for additional information on this setting.
Direct Access Number — F192
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — No
Minimum — 0
Maximum — Max. Freq. (F011)
Units — Hz
V/f Five-Point 2 Voltage
Program Special V/f 5-Point Setting
The V/f 5-Point 2 Voltage establishes the output voltage level that is to be
associated with the frequency setting of F192 (V/f 5-Point 2 Frequency).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number — F193
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — V or % (F701)
Units — V or % (F701)
F191 F193