104 GX9 ASD Installation and Operation Manual
V/f Five-Point 3 Frequency
Program Special V/f 5-Point Setting
The V/f Five-Point 3 Frequency sets the frequency to be associated with the
voltage setting of parameter F195 (V/f 5-Point 3 Voltage).
See F190 and F191 for additional information on this setting.
Direct Access Number — F194
Parameter Type — Numerical
Factory Default 0
Changeable During Run — No
Minimum — 0
Maximum — Max. Freq. (F011)
Units — Hz
V/f Five-Point 3 Voltage
Program Special V/f 5-Point Setting
The V/f 5-Point 3 Voltage establishes the output voltage level that is to be
associated with the frequency setting of F194 (V/f 5-Point 3 Frequency).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number — F195
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — V or % (F701)
Units — V or % (F701)
V/f Five-Point 4 Frequency
Program Special V/f 5-Point Setting
The V/f Five-Point 4 Frequency sets the frequency to be associated with the
voltage setting of parameter F197 (V/f 5-Point 4 Voltage).
See F190 and F191 for additional information on this setting.
Direct Access Number — F196
Parameter Type — Numerical
Factory Default 0
Changeable During Run — No
Minimum — 0
Maximum — Max. Freq. (F011)
Units — Hz
V/f Five-Point 4 Voltage
Program Special V/f 5-Point Setting
The V/f 5-Point 4 Voltage establishes the output voltage level that is to be
associated with the frequency setting of F196 (V/f 5-Point 4 Frequency).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number — F197
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — V or % (F701)
Units — V or % (F701)
V/f Five-Point 5 Frequency
Program Special V/f 5-Point Setting
The V/f Five-Point 5 Frequency sets the frequency to be associated with the
voltage setting of parameter F199 (V/f 5-Point 5 Voltage).
See F190 and F191 for additional information on this setting.
Direct Access Number — F198
Parameter Type — Numerical
Factory Default 0
Changeable During Run — No
Minimum — 0
Maximum — Max. Freq. (F011)
Units — Hz
F194 F198