EasyManuals Logo

Toshiba GX9 User Manual

Toshiba GX9
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
GX9 ASD Installation and Operation Manual 105
V/f Five-Point 5 Voltage
Program Special V/f 5-Point Setting
The V/f 5-Point 5 Voltage establishes the output voltage level that is to be
associated with the frequency setting of F198 (V/f 5-Point 5 Frequency).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number — F199
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — V or % (F701)
Units — V or % (F701)
Frequency Priority Selection
Program Fundamental Standard Mode Selection
Either Frequency Mode 1 (F004) or Frequency Mode 2 (F207) may control
the output frequency of the ASD. This parameter determines which of the two
will control the output frequency and the conditions in which control will be
switched from one to the other.
The Frequency Source 1 or Frequency Source 2 selection specifies the source
of the input frequency command signal (Frequency Mode 1 or 2).
Select Frequency Source 1 for Frequency Mode 1 control.
Select Frequency Source 2 for Frequency Mode 2 control.
If Frequency Source Priority 1 is selected here, the ASD will follow the
control of the Frequency Mode 1 setting for the duration that the commanded
frequency of Frequency Mode 1 is greater than the setting of F208. If the
commanded frequency of Frequency Mode 1 is less than or equal to the setting
of F208, the ASD will follow the setting of Frequency Mode 2.
If Frequency Source Priority 2 is selected here, the ASD will follow the
control of the Frequency Mode 2 setting for the duration that the commanded
frequency of Frequency Mode 2 is greater than the setting of F208. If the
commanded frequency of Frequency Mode 2 is less than or equal to the setting
of F208, the ASD will follow the setting of Frequency Mode 1.
If Frequency Source Priority Switching is selected here, the ASD will follow
the control of the discrete input terminal assigned the function of Terminal
Frequency Priority. The discrete terminal Terminal Frequency Priority will
toggle control to and from the Frequency Mode 1 and Frequency Mode 2
selections for the duration of each activation/deactivation.
Settings:
0 — Frequency Source 1
1 — Frequency Source 2
2 — Frequency Source 1 Priority
3 — Frequency Source 2 Priority
4 — Frequency Source Priority Switching
Direct Access Number — F200
Parameter Type — Selection List
Factory Default Frequency Source 1
Changeable During Run — Yes