GX9 ASD Installation and Operation Manual 195
MON1 Terminal Meter Selection
Program Terminal Analog Output Terminals
This parameter is used to set the output function of the MON1 analog output
terminal. The available assignments for this output terminal are listed in Table 9
on pg. 221.
The MON1 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note: The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (D/N 58686) for
more information on the function of this terminal.
MON1 Terminal Meter Setup Parameters
F672 — MON1 Output Function
F673 — MON1 Terminal Meter Adjustment
Direct Access Number — F672
Parameter Type — Selection List
Factory Default Output Voltage
Changeable During Run — Yes
MON1 Terminal Meter Adjustment
Program Terminal Analog Output Terminals
This parameter is used to set the gain of the MON1 output terminal and is used
in conjunction with the settings of parameter F672.
See parameter F672 for more information on this setting.
Direct Access Number — F673
Parameter Type — Numerical
Factory Default 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
MON2 Terminal Meter Selection
Program Terminal Analog Output Terminals
This parameter is used to set the output function of the MON2 analog output
terminal. The available assignments for this output terminal are listed in Table 9
on pg. 221.
The MON2 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note: The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (D/N 58686) for
more information on the function of this terminal.
MON2 Terminal Meter Setup Parameters
F674 — MON2 Output Function
F675 — MON2 Terminal Meter Adjustment
Direct Access Number — F674
Parameter Type — Selection List
Factory Default Compensated
Frequency
Changeable During Run — Yes
MON2 Terminal Meter Adjustment
Program Terminal Analog Output Terminals
This parameter is used to set the gain of the MON2 output terminal and is used
in conjunction with the settings of parameter F674.
See parameter F674 for more information on this setting.
Direct Access Number — F675
Parameter Type — Numerical
Factory Default 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280