198 GX9 ASD Installation and Operation Manual
Low Output Disable Start Level (Hz)
Program Special Low Output Disable Function
The Low Output Disable Start Level sets the output frequency threshold that,
if exceeded, will initiate the LOD function if properly configured.
Direct Access Number — F732
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Low Output Disable Start Time
Program Special Low Output Disable Function
The Low Output Disable Start Time sets the amount of time that the LOD
Start Level criteria must be met and maintained for the LOD function to be
initiated.
Direct Access Number — F733
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Low Output Disable Setpoint Boost (Hz)
Program Special Low Output Disable Function
The Low Output Disable feature adds the user-input frequency value to the
commanded frequency.
Direct Access Number — F734
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Low Output Disable Boost Time
Program Special Low Output Disable Function
The Low Output Disable Boost Time sets the on-time timer for the LOD
Boost function.
Once expired, the LOD Boost function ceases.
Direct Access Number — F735
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Low Output Disable Feedback Level (Hz)
Program SpecialLow Output Disable Function
The Low Output Disable Feedback Level sets a frequency level that, until the
output of the ASD drops below this setting, the Restart Delay Timer does not
start.
Direct Access Number — F736
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Low Output Disable Restart Delay Time
Program Special Low Output Disable Function
The Low Output Disable Restart Delay Time sets the time that, once expired
and all standard ASD requirements are met, normal ASD operation resumes.
Direct Access Number — F737
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
F732 F737