E6581595
C-19
3
Setting of motor electronic thermal protection level 1  (Same as f173)
If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor
is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1  so
that it fits the motor's rated current.
* If the indications are in percentages (%), then 100% equals the inverter's rated output current (A).

×1.0
Output frequency (Hz)
Output current reduction facto
r
[%]
/
[A]
0
Note) The start level for motor overload reduction is fixed at 6 Hz.
6Hz

×0.6
2) Motor 150%-overload time f607
Parameter f607 is used to set the time elapsed before the motor trips under a load of 150% (overload trip
2) within a range of 10 to 2400 seconds.
3) Inverter overload characteristics
Set to protect the inverter itself. The setting of this parameter cannot be turned to off.
When an inverter overload trip () operates, operation can be improved by lowering stall operating level
, or increasing acceleration time  and deceleration time .
Inverter overload protection characteristic
100%: Inverter rated output current
time [s]
Inverter overload
Monitored output current [%]
0
110% 150%
Current [%]
Inverter overload time [s]
(Outline data)
111 2400
120 242
130 120
140 80
150 60
175 3
200 0.5
60

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required

Related product manuals