6.8 Time limit for lower-limit frequency operation
 : Time limit for lower-limit frequency operation
 : Hysteresis for lower-limit frequency operation
Function
If operation is carried out continuously at a frequency below the lower-limit frequency () for the period
of time set with , the inverter will automatically slow down the motor to a stop. At that time,
” is displayed (alternately) on the operation panel.
This function will be canceled if a frequency command above the lower-limit frequency () 
(Hz).
[Parameter setting]
Title Function Adjustment range Default setting

Time limit for lower-limit frequency
operation
0.0: Disabled
0.1 - 600.0 (s)
0.0

Hysteresis for lower-limit frequency
operation
0.0- (Hz) 0.2
Note: This function is valid when doing forward/reverse switching.
When starting operation, does not operate until output frequency reaches ll.
Output frequency [Hz]
+

Foward / reverse
Time [s]

ON
OFF
