E6581595
F-37
6
6.14 Setting motor constants
 : Auto-tuning
 : Motor rated current
 : Slip frequency gain  : Motor no-load current
 : Automatic torque boost value  : Motor rated speed
 : Motor rated capacity  : Load inertia moment ratio
To use vector control, automatic torque boost and automatic energy saving, motor constant setting (motor tuning)
is required. The following three methods are available to set motor constants.
1) Using the torque boost setting macro function () for setting the V/F control mode selection () and
auto-tuning () at the same time
2) Setting V/F control mode selection () and auto-tuning () independently
3) Combining the V/F control mode selection () and manual tuning
Caution:
If the settings for V/F control mode selections  are : automatic torque boost control, : vector control,
: energy saving.
Look at the motor's name plate and set the following parameters.
: Base frequency 1 (rated frequency)
: Base frequency voltage 1 (rated voltage)
: Motor rated capacity
: Motor rated current
: Motor rated speed
Set the other motor constants as necessary.
[Selection 1: Setting by parameter setting macro torque boost]
This is the easiest of the available methods. It conducts vector control and auto-tuning at the same time.
Be sure to set the motor for , , , ,  .
Set  to (Automatic torque boost + auto-tuning)
Set  to (Vector control + auto-tuning)
Set  to (Energy-saving + auto-tuning)
Refer to section 5.4 for details of the setting method.

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required

Related product manuals