6.6 Operation frequency
6.6.1 Starting frequency
 : Starting frequency
Function
The frequency set with  is put out as soon as operation is started.
Use the  parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title Function Adjustment range Default setting

Starting frequency 0.1-10.0 (Hz) 0.5
6.6.2 Run/stop control with frequency setting signals
 : Operation starting frequency
 : Operation starting frequency hysteresis
Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title Function Adjustment range Default setting

Operation starting frequency 0.0- (Hz) 0.0

Operation starting frequency hysteresis 0.0- (Hz) 0.0
0 A B 100% Frequency command value
 + 
 - 

When the frequency command signal
reaches the B point, the inverter
operates.
When decelerating, operation stops
when the frequency setting signal is less
than point A.
Output frequency [Hz]
