E6581595
F-18
6
Starting frequency 
Output frequency (Hz)
0
Operation signal (F-CC)
Time
ON
OFF
6.6 Operation frequency
6.6.1 Starting frequency
 : Starting frequency
Function
The frequency set with  is put out as soon as operation is started.
Use the  parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title Function Adjustment range Default setting

Starting frequency 0.1-10.0 (Hz) 0.5
6.6.2 Run/stop control with frequency setting signals
 : Operation starting frequency
 : Operation starting frequency hysteresis
Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title Function Adjustment range Default setting

Operation starting frequency 0.0- (Hz) 0.0

Operation starting frequency hysteresis 0.0- (Hz) 0.0
0 A B 100% Frequency command value
 + 
 - 

When the frequency command signal
reaches the B point, the inverter
operates.
When decelerating, operation stops
when the frequency setting signal is less
than point A.
Output frequency [Hz]


Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required

Related product manuals