8.2 Status monitor mode
8.2.1 Status monitor under normal conditions
In this mode, you can monitor the operation status of the inverter.
To display the operation status during normal operation:
Press the MODE key twice.
Setting procedure (eg. operation at 60Hz)
Item displayed
Panel
operated
LED
display
Communic
ation No.
Description
Output frequency
*

The output frequency is displayed (Operation at
60Hz). (When standard monitor display selection
 [output frequency])
Parameter setting
mode

The first basic parameter ” (history function)
is displayed.
Direction of
rotation

FE01
The direction of rotation is displayed.
(: forward run, : reverse run)
Frequency
command value *

FE02
The frequency command value (Hz/free unit) is
displayed.
( In case of = )
Output current *

FE03
The inverter output current (load current) (%/A) is
displayed.
( In case of = )
Input voltage *

FE04
The inverter input voltage (DC detection) (%/V) is
displayed.
( In case of = )
Output voltage *

FE05
The inverter output voltage (%/V) is displayed.
( In case of = )
Inverter
load factor *

FE27
The inverter load factor (%) is displayed.
( In case of = )
Output frequency
*

FE00
The output frequency (Hz/free unit) is displayed.
( In case of = )
(Continued overleaf)
* Monitor items can be selected by setting parameters  to , (). Refer to Note 11.
Refer to page H-8 for notes.
Note 2
Note 3
MODE
MODE

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required