EasyManua.ls Logo

Toshiba TOSVERT VF-nC3

Toshiba TOSVERT VF-nC3
254 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6581595
E-21
5
5) Use a motor that has 2-8 P.
6) Always operate the motor in single operation (one inverter to one motor). Sensorless vector control cannot
be used when one inverter is operated with more than one motor.
When using a combination of several motors, set the V/F constant (=).
7) The maximum length of wires between the inverter and motor is 30 meters. If the wires are longer than 30
meters, set standard auto-tuning with the wires connected to improve low-speed torque during sensorless
vector control.
However the effects of voltage drop cause motor-generated torque in the vicinity of rated frequency to be
somewhat lower.
8) When a reactor is connected between the inverter and a motor, the motor's generated torque may fall.
Setting auto-tuning may also cause a trip () rendering sensorless vector control unusable.
5.12 Manual torque boost - increasing torque boost at low
speeds
 : Torque boost 1
Function
If torque is inadequate at low speeds, increase torque by raising the torque boost rate with this
parameter.
Output voltage
[V]/(%)
Base frequency voltage
Output frequency (Hz)

Base frequency


[Parameter setting]
Title Function Adjustment range Default setting

Torque boost value 1 0.0 - 30.0 (%)
According to model
(Refer to section 11.4)
Valid when  is set to 0 (V/F constant) or 1 (square reduction)
Note 1: The optimum value is programmed for each inverter capacity. Be careful not to increase the torque boost
rate too much because it could cause an overcurrent trip at startup.

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Related product manuals