Parameterizing and Configuring
Configuring the devices at EtherNet/IP
124
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
n Input data– TBEN-S1-8DIP-D [}44]
status word + 7 words
Word no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status
0x0000 - FCE - - - COM V1 - - - - - - - ARGEE Diag
Warn
IN
0x0001 - - - - - - - - DI7
C7P4
DI6
C6P4
DI5
C5P4
DI4
C4P4
DI3
C3P4
DI2
C2P4
DI1
C1P4
DI0
C0P4
Deactivate diagn.
0x0002 - - - - - - - - VERR
V1
C7
VERR
V1
C6
VERR
V1
C5
VERR
V1
C4
VERR
V1
C3
VERR
V1
C2
VERR
V1 C1
VERR
V1
C0
Latch IN
0x0003 - - - - - - - - DI7 DI6 DI5 DI4 DI3 DI2 DI1 DI0
CNT Ch0
0x0004 Counter value LSB
0x0005 Counter value MSB
Freq. Ch0
0x0006 Frequency MSB Frequency LSB
Module
status
0x0007 -
n Output data – TBEN-S1-8DIP-D [}53]
control word + 2 words
Word no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Control
0x0000 - - - - - - - - - - - - - - - -
Latch
reset
0x0001 - - - - - - - - DI7 DI6 DI5 DI4 DI3 DI2 DI1 DI0
Counter
reset
0x0002 - - - - - - - - - - - - - - - CNT
reset