EasyManuals Logo

turck TBEN-S Series User Manual

turck TBEN-S Series
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #182 background imageLoading...
Page #182 background image
Operating
Measurement value representation of analog modules
182
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
9.3 Measurement value representation of analog modules
9.3.1 Measurement value representation – TBEN-S2-4AI
Voltage – standard
-10…10 V Diagnostics decimal hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 3.052 × 10
-4
) V
> 10.1000 V "Upper limit value exceeded” ON 32767 7FFF
< 10.0500 V "Upper limit value exceeded" OFF 32767 7FFF
10.0000 V Nominal range 32767 7FFF
9.991 V 32736 7FE0
0.005 V 16 0010
0 V 0 0000
-0.0050 V -16 FFF0
-9.995 V -32752 8010
-9.999 V -32767 8001
-10.0000 V -32768 8000
> -10.0500 V "Lower limit value underrun" OFF -32768 8000
> -10.1000 V "Lower limit value underrun" ON -32768 8000
0…10 V Diagnostics decimal hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 3.052 × 10
-4
) V
> 10.1000 V "Upper limit value exceeded” ON 32767 7FFF
< 10.0500 V "Upper limit value exceeded" OFF 32767 7FFF
10.0000 V Nominal range 32767 7FFF
9.991 V 32736 7FE0
0.005 V 16 0010
0 V 0 0000
> -0.0500 V "Lower limit value underrun" OFF 0 0000
> -0.10000 V "Lower limit value underrun" ON 0 0000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the turck TBEN-S Series and is the answer not in the manual?

turck TBEN-S Series Specifications

General IconGeneral
Brandturck
ModelTBEN-S Series
CategoryControl Unit
LanguageEnglish

Related product manuals