Technical Data
Technical data – TBEN-S2-4AI
236
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
14.10.2 Measurement error total (FSR)
Operation mode RTD/resistance
Measurement range 2-wire 3-wire 4-wire
Pt100 -200 °C…850 °C ≤ 0.85 %
Pt 100 -200 °C…150 °C ≤ 0.85 % ≤ 0.95 % ≤ 0.85 %
Pt 200 -200 °C…850 °C ≤ 1.35 % ≤ 0.85 % ≤ 0.95 %
Pt 200 -200 °C…150 °C ≤ 0.85 %
Pt 500 -200 °C…850 °C ≤ 0.3 % ≤ 0.85 %
Pt 500 -200 °C…150 °C ≤ 1.35 % ≤ 0.85 % ≤ 0.85 %
Pt 1000 -200 °C…850 °C ≤ 0.85 %
Pt 1000 -200 °C…150 °C ≤ 0.95 % ≤ 0.85 % ≤ 0.85 %
Ni 100 -60 °C…250 °C ≤ 0.85 % ≤ 0.95 % ≤ 0.85 %
Ni 100 -60 °C…150 °C ≤ 1.35 % ≤ 0.95 % ≤ 0.85 %
Ni 1000 -60 °C…250 °C ≤ 1.35 % ≤ 0.95 % ≤ 0.85 %
Ni 1000 -60 °C…150 °C ≤ 1.35 % ≤ 0.85 % ≤ 0.85 %
0…100 Ω ≤ 0.85 % ≤ 0.95 % ≤ 0.85 %
0…400 Ω ≤ 0.85 %
0…2 kΩ ≤ 0.85 %
0…4 kΩ ≤ 0.85 %
Operation mode thermocouple
Measurement range
Type K -270…1370 °C ≤ 1.35 % Only valid for lower measure-
ment range
Type B 100…1820 °C ≤ 1.15 %
Type E -270…1000 °C ≤ 1.65 % Only valid for lower measure-
ment range
Type J -210…1200 °C ≤ 0.75 %
Type N -270…1300 °C ≤ 0.75 %
Type R -50…1768 °C ≤ 0.85 %
Type S -50…1768 °C ≤ 0.85 %
Type T -200…400 °C ≤ 1.35 % Only valid for lower measure-
ment range
Type C 0…2315 °C ≤ 0.75 %
Type G 0…2315 °C ≤ 2.25 % Only valid for lower measure-
ment range