Parameterizing and Configuring
Configuring the devices at EtherNet/IP
162
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Class 171 (0xAB) – VAUX Control
This class contains parameters for of the 24 VDC sensor/ actuator supply.
Applies to:
n TBEN-S2-8DIP
Attribute no. Designation Get/Set Type Meaning
Dec. Hex.
Parameters
1 0x01 VAUX1 pin1 C0 (Ch0/1) G/S USINT 0: 24 VDC
1: switchable
2: off
2 0x02 VAUX1 Pin1 C1 (Ch2/3) G/S USINT 0: 24 VDC
1: switchable
2: off
3 0x03 VAUX1 pin1 C2 (Ch4/5) G/S USINT 0: 24 VDC
1: switchable
2: off
4 0x04 VAUX1 Pin1 C3 (Ch6/7) G/S USINT 0: 24 VDC
1: switchable
2: off
5 0x05 VAUX1 pin1 C0 (Ch0/1) G USINT 0: on
1: off
6 0x06 VAUX1 Pin1 C1 (Ch2/3) G USINT 0: on
1: off
7 0x07 VAUX1 pin1 C2 (Ch4/5) G USINT 0: on
1: off
8 0x08 VAUX1 Pin1 C0 (Ch0/1) G USINT 0: on
1: off
Class 188 (0xBC) – Basic
This class data and parameters for the device’s basic functions.
Applies to:
n TBEN-S1-4DXP
Attr. no. Designation Get/
set
Type Meaning
Dec. Hex.
Parameters
1 0x01 Activate output Ch0 G/S USINT 0: no
1: yes
2 0x02 Activate output Ch1 G/S USINT 0: no
1: yes
3 0x03 Activate output Ch2 G/S USINT 0: no
1: yes