Operating
Measurement value representation of analog modules
188
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
-1…1 V Diagnostics decimal hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 3.6164 × 10
-5
) V
> 1.176 V "Upper limit value exceeded” ON >32519 > 7F07
< 1.160 V "Upper limit value exceeded" OFF > 32076 < 7DC4
1.185 V Nominal range 32767 7FFF
1.175 V 32512 7F00
1 V 27651 6C03
0.593 V 16384 4000
0 V 0 0000
-0.5930 V -16384 C000
-1 V -27651 93FD
-1.175 V -32512 8100
-1.185 V -32768 8000
> -1.160 V "Lower limit value underrun" OFF > -32076 > 82B4
< -1.176 V "Lower limit value underrun" ON > -32519 < 80F9
-500…500 mV Diagnostics decimal hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 1.8085 × 10
-2
) mV
> 588 mV "Upper limit value exceeded” ON > 32513 > 7F01
< 580 mV "Upper limit value exceeded" OFF > 32071 < 7D47
592.6 mV Nominal range 32767 7FFF
587.9 mV 32512 7F00
500.0 mV 27647 6BFF
296.3 mV 16384 4000
0 mV 0 0000
-296.3 mV -16384 C000
-500.0 mV -27647 9401
-587.9 mV -32512 8100
-592.6 mV -32768 8000
< -580 mV "Lower limit value underrun" OFF > -32071 > 82B9
> -588 mV "Lower limit value underrun" ON < -32513 < 80FF