Operating
Measurement value representation of analog modules
198
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
-20…20 mA Diagnostics Decimal hexadecimal
(two's complement)
Current value I
M
= (dec. value × 10
-4
) mA
> 22.00 mA "Overload/Overcurrent" ON > 22000 > 55F0
< 21.80 mA "Overload/Overcurrent" OFF > 21800 > 5528
> 21.00 mA "Upper limit value exceeded” ON > 21000 > 5208
< 20.50 mA "Upper limit value exceeded" OFF > 20500 > 5014
22.00 mA Nominal range 22000 55F0
21.00 mA 21000 5208
10.00 mA 10000 2710
4.00 mA 4000 0FA0
0.00 mA 0 0000
-10.00 mA -10000 D8F0
-21.00 mA -21000 ADF8
-22.00 mA -22000 AA10
> -20.50 mA "Lower limit value underrun" OFF > -20500 > AFEC
< -21.00 mA "Lower limit value underrun" ON > -21000 < ADF8
> -21.80 mA "Underflow" OFF > -21800 > AAD8
< -22.00 mA "Underflow" ON > -22000 < AA10