RTD (with extended temperature range)
n Pt100/Pt200/Pt500/Pt1000, temperature range -200…850 °C, -328…1562 °F
Celsius
Measured value Diagnostics Decimal hexadecimal
(two's complement)
> -202 °C "Lower limit value underrun" ON -2020 F81C
-200 °C Nominal range -2000 F830
-135°C -1350 FABA
-1 °C -10 FFF6
0 °C 0 0000
1 °C 10 000A
850 °C 8500 2134
858.5 °C "Upper limit value exceeded” ON 8585 2189
Fahrenheit
Measured value Diagnostics Decimal hexadecimal
(two's complement)
> -331.6 °F "Lower limit value underrun" ON -1658 F986
> -328 °F Nominal range -1640 F998
< -211°F -1055 FBE1
30.2 °F 151 0097
32 °F 160 00A0
33.8 °F 169 00A9
1562 °F 7810 1482
1577.3 °F "Upper limit value exceeded” ON 7886 1ECE
n Ni100/Ni1000, temperature range -60…250 °C, -76…482 °F
Celsius
Measured value Diagnostics Decimal hexadecimal
(two's complement)
> -60.6 °C "Lower limit value underrun" ON -606 FDA2
- 60C Nominal range -600 FDA8
-1°C -10 FFF6
0 °C 0 0000
1 °C 10 000A
250 °C 2500 09C4
252.5 °C "Upper limit value exceeded” ON 2525 09DD