Parameterizing and Configuring
Parameters – overview
42
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Parameters – TBEN-S2-4AO
Parameter name Value Meaning Description
Dec. Hex.
DCH Deactivate channel
0 0x00 No
Channel active
1 0x01 Yes Channel inactve
DDI Deactivate
diagnostics
0 0x00 No
Diagnostics active
1 0x01 Yes Diagnostics inactive
DRE Data representa-
tion
0 0x00 Standard
1 0x01 NE43
2 0x02 Extended range
FFB Output on fieldbus
error
0 0x00 default value
The outputs are set to this
defined value in case of a
fieldbus error.
1 0x01 Substitute value
2 0x02 Current value
IRA Current range
0 0x00 0…20 mA
Set the measurement
range of the current out-
put.
1 0x01 4…20 mA
OPM Operation mode
0 0x00 Voltage
The output is defined as a
voltage output.
1 0x01 Current The output is defined as a
current output.
ORM Output
recovery mode
0 0x00 Automatic
The output switches-on
autmatically as soon as
the overload has been
eliminated.
1 0x01 Manual The output has to be
switched-on manually as
soon as the overload has
been eliminated.
SVAL Substitute value Defining the substitute
value for the analog out-
put.
URA Voltage range
0 0x00 -10…10 V
Set the measurement
range of the voltage out-
put.
1 0x01 0…10 V
2 0x02 2…10 V
3 0x03 0…5 V
4 0x04 1…5 V