Parameterizing and Configuring
Configuring devices at Modbus TCP
84
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Register no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0x0008 - FCE - - - COM V1 - - - - - - - ARGEE Diag
Warn
TBEN-S1-4DXP – output registers
Meaning of the process output data [}53]
Register no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
OUT
0x0800 - - - - - - - - - - - - DX3
C3P4
DX2
C2P4
DX1
C1P4
DX0
C0P4
Latch reset
0x0801 - - - - - - - - - - - - DX3 DX2 DX1 DX0
CNT reset
0x0802 - - - - - - - - - - - - - - - CNT
reset
PWM Ch3
0x0803 - - - - - - - - Duty Cycle
TBEN-S1-4DXP – parameter registers
Parameter description [}39]
Register no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 0…channel 7
0xB000 - - - - EN
DO3
EN
DO2
EN
DO1
EN
DO0
- - - - SRO3 SRO2 SRO1 SRO0
Channel 0
0xB001 IST DX0 DIFT
DX0
DMOD_CNT DX0
Channel 1
0xB002 IST DX1 DIFT
DX1
DMOD DX1
Channel 2
0xB003 IST DX2 DIFT
DX2
DMOD DX2
Channel 3
0xB004 IST DX3 DIFT
DX3
DMOD_PWM DX3