EasyManua.ls Logo

UFactory xArm6 - PLC Communication & Analog I;O Usage

UFactory xArm6
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
Users must follow the electrical specifications set in the 2.4.1 ‘universal specification’.
This example shows how a simple button is connected to a digital input.
2.4.3.3. Communicate with other Machines or PLCs
If general GND (0V) is established and the machine uses open-drain output
technology, digital I/O and other can be used device communication, see the figure
below.
2.4.4. General Analog I/O
This type of interface can be used to set or measure voltage (0-10V) going into or out
of other devices.
For the highest accuracy, the following instructions are recommended:
Use the GND terminal closest to this I/O.
The device and Control box use the same ground (GND). The analog I/O is not
isolated from the control box.
Use shielded cables or twisted pairs. Connect the shield to the “GND” terminal on
the “Power” section.

Table of Contents

Related product manuals