When the <PRV> or <NXT> key is pressed, the previous or next setting is selected and value
entered in the current menu is automatically stored.
The following settings in the configuration menu (menu 1.2.1 up to menu 1.2.16) can be set:
Menu Description Range Remark
1.2.1
Max. flow Flowmeter-1 at 20 mA 0...32,000 m3/h The value to be entered is the maximum flow of the
overboard discharge flow connected to the Oil
discharge monitoring and control system, if fitted.
1.2.2
Max. flow Flowmeter-2 at 20 mA 0...32,000 m3/h The value to be entered is the maximum flow of the
overboard discharge flow connected to the Oil
discharge monitoring and control system, if fitted.
In case of flowmeter-1 only, this setting must be set 0.
1.2.3
K-factor skid flow meter 0…10,000 pulse/l THIS FACTOR MAY NOT BE CHANGED
This is the k-factor of the flow meter (flow sensor)
installed in the skid.
This factor is normally factory set and is mentioned
on tag plate of flow meter (flow sensor).
1.2.4
Flow Configuration Separated / Combined This function makes it possible to COMBINE TWO FLOW
METERS, IF FITTED BOTH.
The system will choose the correct flow metering
system based on current flow rate.
The combined system option is only valid with older EPU
versions
See drawing 0806-8038 for configuration of the
separated system.
1.2.5
K-factor measuring cell 0 0…10,000 THIS FACTOR MAY NOT BE CHANGED
This is the k-factor of the measurement cell installed
in the skid.
This factor is normally factory set and is mentioned
on tag plate of cell.
1.2.6
Ship speed GPS / Ship's log The value entered determines whether the input of
the GPS or the ship's log is used to calculate the
ship's speed.
1.2.7
K-factor Ships log 0…400 pulse/NM The value entered is the input in pulses/nautical mile
from the vessel's speed log (if installed).
1.2.8
Total ship's volume 0…600 kTon The Value to be entered is the ships deadweight in
kilo tons. In other words if the deadweight is 45,000
tons, a value of 45 must be entered
1.2.9
Status of the ship New / Old Value to be entered is either New or Old based on
IOPP certificate Item 1.7
1.2.10
Number of sample points 1…6 The value to be entered is based on the number of
sampling points installed on the ship.
1.2.11
...
1.2.16
Name of sample point - port high
- starboard high
- port low
- starboard low
- stripping
- segregated ballast
The value to be entered is based on the name or
nomination of each particular sample point.
The sample points:
- port high
- starboard high
- port low
- starboard low
- stripping
are used for dirty/clean ballast (Relay X6)
The sample point:
- segregated
is used for segregated ballast (Relay X7)