7.2.1.5.4.2 Shutdown mode (menu 1.5.3.2)
The shutdown mode is entered when the <STOP> key is pressed in menu 1.5.3.
If the shutdown mode is entered from idle mode (menu 1.5.3) the system will initiates a shutdown
sequence.
The shutdown sequence consists of approximately 2 minutes backward flush and 2 minutes forward
flush. After completion of the sequence the piping of the system has been cleaned, leaving the
system in a clean condition for the next discharge run and the system will return to standby mode
(menu 1).
Figure 50
CONTROL Sample point: 1 22-11-11
shutdown Oil type: 5 10:38
Concentration A 0 PPM discharge
Flow A 0 m3/h dirty
Skid Flow 0 l/h com: C
Speed A 10.0 kts pos: C
Discharge rate 0.0 l/nm segregated
Total oil 2.1 l com: C
Latitude 5321.756N pos: C
Longitude 00711.854E
Backflush
EPU: OK
free: 1927296 kB