80
Figure 69
31. In the case of this vessel, check that the valves have indeed been operated. On the display
of the MCU this is indicated by the change of POS: from “C” to “O”.
32. The discharged oil indicated on the display by “Total oil” will increase. Allow the oil discharge
to increase till it reaches 40 litres.
Figure 70
33. When the “Total oil” reaches 40 litres the signal will be given to close the overboard valve
and to open the slop tank valve and an alarm is triggered.
Figure 71
34. Press the <ACK> key to stop the alarm buzzer.
35. In the case of this vessel, check that the valves have indeed been operated.
36. Press the <STOP> key to return to “idle mode”.
37. Press the <STOP> key again to return to “standby mode”.
38. Press the <SETUP> key to enter the “setup mode”.
39. Press the <CHANGE> key and press the <NXT> key until “reset oil total” is displayed.
40. Change the “reset oil total” to “Yes”.
CONTROL Sample point: 1 22-11-11
sample Oil type: 5 10:38
Concentration M 400 PPM discharge
Flow M 1000 m3/h dirty
Skid Flow 0 l/h com: O
Speed M 15.0 kts pos: O
Discharge rate 0.0 l/nm segregated
Total oil 0.0 l com: C
Latitude 5321.756N pos: C
Longitude 00711.854E
EPU: OK
free: 1927296 kB
MORE? STOP
CONTROL Sample point: 1 22-11-11
sample Oil type: 5 10:38
Concentration M 400 PPM discharge
Flow M 1000 m3/h dirty
Skid Flow 0 l/h com: C
Speed M 15.0 kts pos: C
Discharge rate 0.0 l/nm segregated
Total oil 40.0 l com: C
Latitude 5321.756N pos: C
Longitude 00711.854E
EPU: OK
free: 1927296 kB
MORE? STOP
CONTROL Sample point: 1 22-11-11
alarm Oil type: 5 10:38
ALAR M
Total oil discharge limit
EPU: no communication
free: 1927296 kB
ACK