APPENDIX 3_________________________________________________________________________
112____________________________________________________________________M210492EN-A
>send 22
RH= 24.4 %RH T= 29.1 'C
Disconnect the terminal.
Check that the jumpers in connector X4 are in the right places.
X4
X4
X1 X2
Remount the RS 485/422 serial module.
Close the cover.
Repeat this setting procedure with each transmitter.
When all transmitters on the network have been configured,
switch them off.
Checking the serial port network operation
Normally measurement readings are asked when the transmitter is in
POLL mode; then the command must include the address of the
transmitter. If the settings of the transmitter need to be changed, the
transmitter is switched to STOP mode with command OPEN;
commands can then be given without address. When the line to the
transmitter is closed, it returns to POLL mode.
STOP mode
Open the line to the transmitter:
open 22<cr>
DMP 22 line opened for operator commands
Transmitter no. 22 is now temporarily set to STOP mode; it accepts
commands sent without address until CLOSE command is given.
Individual settings can now be easily modified. Do not open more
than one line at a time.