VAMP 24h support phone +358 (0)20 753 3264
Overcurrent stages I>> and I>>> (50/51)
0.10 – 20.00 x In (I>>)
0.10 – 40.00 x In (I>>>)
0.04
**)
– 1800.00 s (step 0.01 s)
0.04
**)
– 300.00 s (step 0.01 s)
Transient over-reach, any
±3% of the set value or 5 mA secondary
**) This is the instantaneous time i.e. the minimum total operational time including the fault
detection time and operation time of the trip contacts.
Thermal overload stage T> (49)
0.1 – 2.40 x In
(step 0.01)
Cooling time coefficient:
1.0 – 10.0 xTau (step 0.1)
Resetting ratio (Start & trip)
NOTE! Stage is blocked when motor has been running for 2 seconds.
Secondary current has to be > 1A in all phases.
Undercurrent protection stage I< (37)
Definite time characteristic:
0.3 – 300.0s s (step 0.1)
±2% of set value or ±0.5% of the rated value
NOTE! Stage Blocking is functional when all phase currents are below the block
limit.