Series 651 INSTALLATION
605451EC Edition 2014-07-10 39/
Local operation:
(‘Control Performance Analyzer’ or ‘Service Box 2‘)
Remote operation:
• With CPA, do configuration in menu
‘Interface / Setup’.
• With SB2, do configuration in menu ‘Setup
/ Interface’.
It’s not possible to do ‘Interface
configuration‘ via remote operation.
4.5.3 Valve configuration
Basic valve configuration must be adapted according to application needs.
Definition of valve plate position in case of:
• After power up, default is ‘close‘.
• Power failure, default is ‘not defined‘. Only for versions that have Power Fail Option equipped [651 . .
- . . C . - . . . . or 651 . . - . . H . - . . . . ].
• Network failure, default setting refer to individual product data sheet.
Local operation:
(‘Control View’, ‘Control Performance Analyzer’
or ‘Service Box 2‘)
Remote operation:
With CPA:
• Do valve configuration in menu ‘Valve
/ Setup’.
With SB2:
• Do power up configuration in menu
‘Setup / Valve’.
• Do power fail configuration in menu
‘Setup / Valve’.
It’s not possible to do ‘Valve
configuration‘ via remote operation.