Series 651  INSTALLATION 
 
605451EC  Edition 2014-07-10  43/
 
4.5.2  Pressure control configuration 
Select the configuration what your application needs. 
 
System Configuration 
Constant gas flow available 
Constant gas flow not 
available 
Tv*<= 500 sec  Tv* > 500 sec 
 
Adaptive pressure 
controller 
(Refer to chapter: 
Pressure controller) 
Fixed pressure controller 
(Refer to chapter: Pressure controller) 
 
Fixed pressure controller 
(Refer to chapter: Pressure controller) 
Soft Pump  Soft Pump (Refer to chapter: Pressure controller) 
 
 Use the formula below to define the applicable pressure control algorithm. 
 
 
q
L
  gasflow for learn [mbarl/s] 
p
SFS
  sensor full scale pressure [mbar] 
Tv*
 
Vacuum time constant [sec] 
CV
 
Chamber Volume
 
[l] 
 
 
            P
SFS
 
•
••
• CV
 
Tv = 
 q
L
 
Upstream 
chamber 
valve 
Pump 
Downstream 
chamber 
valve 
Pump