Series 651 
TROUBLE SHOOTING 
 
605451EC  Edition 2014-07-10  71/
 
6  Trouble shooting 
Failure  Check  Action 
No dots lighted on display 
-  24 V power supply ok?  -  Connect valve to power supply according to 
«Electrical connection» and make sure that power 
supply is working. 
Remote operation does not work 
-  Local operation via service 
port active  
-  Switch to remote operation. 
-  Safety mode active, check for 
D on display? 
-  Provide power to motor to allow for operation. 
-  Refer to «Electrical connection» for details. 
(fatal error - limit stop of valve unit 
not detected) 
  -  Reset control unit. Cycle power (OFFON) 
or 
-  Send reset command: 
- local via service port with CV/CPA/Service Box2 
-  If reset unsuccessful, replace actuator according to  
«Maintenance procedures». 
Display shows «
» 
(fatal error - rotation angle of valve 
plate limited during operation) 
-  Valve plate mechanically 
obstructed? 
-  Resolve obstruction. 
-  Reset control unit. Cycle power (OFFON)  
or 
-  Send reset command: 
- local via service port with CV/CPA/Service Box2 
(fatal error - motor driver failure 
detected) 
  -  Replace control unit according to  
«Maintenance procedures». 
Display shows «
» or «
» 
Motor Interlock is open 
-  Motor power supplied?  -  Provide power to motor to allow for operation.  
-  Refer to «Electrical connection» for details. 
(Service Request) 
-  Valve unit heavy 
contaminated or gate seal 
heavyly sticking? 
-  Clean valve and/or replace gate seal according to  
«Maintenance procedures». 
CLOSE VALVE does not work 
-  Safety mode active, check for 
D on display? 
-  Maintenance mode active 
-  Provide power to motor to allow for operation. 
-  Refer to «Electrical connection» for details. 
-  Refer to “Display shows «M  C»” in this table 
OPEN VALVE does not work 
-  Safety mode active, check for 
D on display? 
-  Maintenance mode active 
-  Provide power to motor to allow for operation. 
-  Refer to «Electrical connection» for details. 
-  Refer to “Display shows «M100»” in this table 
Maintenance mode active 
  -  Pin 14 of service connector is connected to ground. 
Plate will close. Further movement of plate is blocked. 
Priority of pin 14 is higher than pin 13. If pin 14 is 
connected to ground after pin 13 the valve will close. 
Ground of service connector is at pin 4 and 8.  
Maintenance mode active 
  -  Pin 13 of service connector is connected to ground. 
Plate will open. Further movement of plate is blocked. 
POSITION CONTROL does not 
work 
-  Safety mode active, check for 
D on display? 
-  Provide power to motor to allow for operation. 
-  Refer to «Electrical connection» for details. 
-  POSITION CONTROL 
selected, check for V on 
display? 
-  Select POSITION CONTROL mode.  
Refer to «Position control» for details. 
COMPRESSED AIR FAILURE 
«AIRf» 
-  No or too less air pressure on 
air input of valve 
-  Connect air or increase air pressure. Make sure that the 
air pressure is more than 4 bar (55 psi). 
COMPRESSED AIR FAILURE at 
Exhaust «AIRx» 
-  Wrong connection of 
compressed air input and 
output 
-  No compressed air at output 
exhaust 
-  Connect compressed air in accordance chapter 
installation. 
 
-  Contact your local VAT service center for support.