INSTALLATION  Series 
 
52/99
Edition 2014-07-10  605451EC
 
4.6.1.1  Gain factor adjustment 
The gain factor effects: Stability, Response time 
 
Default value is 1. Adjustment range is from 0.0001 to 7.5. 
 
Higher gain results in:  faster response    higher over- / undershoot of pressure 
Lower gain results in:   slower response    lower over- / undershoot of pressure 
 
Adjustment procedure: 
 
1.  Start with gain factor 1.0 
2.  Open valve. 
3.  Control a typical pressure / flow situation. 
4.  Repeat from step 2 with lower (higher) gain factors until optimal pressure response is achieved and 
stability is ok. 
 
 
 
Normally adjustments down to gain factors of 0.42 should lead to good results. 
Otherwise you may need to improve sensor connection. Refer to «Requirements to 
sensor connection». 
 
: 
(‘Control View’, ‘Control Performance Analyzer’ 
or ‘Service Box 2‘) 
: 
Set gain factor in menu ‘Setup / Control 
Parameter’ 
It’s not possible to do ‘Gain factor adjustment‘ via 
remote operation.