Ver-Mac 2018 V-Touch Controller for TLDs User Manual – 3.2 43
8.5 System Clock
8.5.1 Master Unit System Clock
The master time is used to log the system events and start schedules. Make sure
that the master unit time is accurate; if not, you need to set it.
The System Clock screen offers two ways of configuring the system clock,
Manually or as a NTP Client. In order to prevent clock time-drift, Ver-Mac
recommends the use of an NTP server. This function is available only to Admin
Users, for TLD master units equipped with a modem connected to the Internet.
Figure 20: Clock Configuration screen for manual configuration
1. Select the time zone that matches the geographic location of the TLD.
2. Adjust the present Date and Time (arrows or keypad input) and Apply.