Pout (kW)
Active output power.
Power Factor
Power factor of output power.
Load percent (%)
Percentage of recent power rated to output power.
5.2.4 Settings Submenu
The settings screen consists of tabs that list UPS settings for configuration and adjusting parameters with tabs for:
• Output
• Battery
• Monitor
• System
NOTE: Do not change parameter settings or reset to factory defaults when powering-off the UPS.
To modify UPS settings:
1. At the main menu, select the Settings icon, and press Enter.
2. Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the parameter
list for the selected tab.
Output Parameter Options
Voltage selection
Nominal voltage setting. Set the nominal system voltage to match the input voltage of the UPS.
• 200 V
• 208 V
• 220 V
• 230 V
• 240 V
• Autodetect
Startup on bypass
Allows the UPS to start-up in bypass mode.
• Enable — Start the UPS in bypass mode
• Disable — Start the UPS in normal mode (default)
Frequency selection
Selects the frequency of the output.
• Auto, Bypass enabled — Automatically detects frequency of utility/mains power and sets the nominal
frequency to match and bypass mode is enabled (default).
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 43
Vertiv™ Liebert® GXT5 UPS Installer/User Guide