8.1 Battery Run Times
NOTE: Run times in this table are approximate. Times are based on new, fully-charged, standard battery modules at a
temperature of 77 °F (25 °C) with 100% resistive UPS loading. Run times listed above can vary by ±5% due to
manufacturing variances of the individual batteries.
Load
Internal
Battery
Only
Number of External Battery Cabinets
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 300 300 74.2 245.3 431.5 619.7 817.3 1023.1 1229.9 1478.7 1632.9 1754.7 1853.3
20 600 600 35.8 133.7 229.1 330.9 438.3 545.2 648.4 777.7 894.8 1013.4 1133.6
30 900 900 21.3 87.2 154.2 219.9 289.8 360.9 435.4 510.7 586.7 655.9 733.8
40 1200 1200 14.6 61.9 114.6 165.6 213.8 266.7 320.9 375.6 431.7 487.1 543.9
50 1500 1500 10.7 46.9 89.0 131.5 172.3 210.5 253.9 296.6 340.8 385.0 430.7
60 1800 1800 8.2 38.6 73.8 108.4 142.3 176.4 208.6 244.3 280.8 317.4 354.1
70 2100 2100 6.4 31.0 59.0 89.3 119.2 148.7 178.5 206.7 236.7 267.5 298.6
80 2400 2400 5.0 25.9 50.0 78.0 103.7 129.1 154.0 180.3 205.0 231.3 258.2
90 2700 2700 4.0 22.2 43.1 67.0 89.3 113.6 136.7 159.4 181.7 203.7 226.8
100 3000 3000 3.3 19.1 38.7 57.9 80.9 101.5 121.0 137.8 157.2 177.0 196.7
Table 8.5 Battery Run Time in Minutes Model: GXT5-3KL620RT2UXL and GXT5-3KL630RT2UXL
Load
Internal
Battery
Only
Number of External Battery Cabinets
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 500 500 120.0 272.5 427.5 582.5 737.5 892.5 1047.5 1202.5 1357.5 1512.5 1667.5
20 1000 1000 59.0 129.0 211.0 294.0 377.0 460.0 543.0 625.5 708.5 791.5 874.5
30 1500 1500 36.5 85.0 133.0 189.5 246.0 303.0 359.5 416.5 473.0 530.0 586.5
40 2000 2000 25.0 62.5 99.0 136.0 179.5 222.5 266.0 309.5 353.0 396.5 439.5
50 2500 2500 18.5 48.0 78.0 107.5 138.0 173.0 208.0 243.0 278.0 313.5 348.5
60 3000 3000 14.5 38.5 63.5 88.0 113.0 138.5 168.0 197.0 226.5 256.0 285.5
70 3500 3500 11.5 31.0 53.0 74.0 95.5 117.0 139.0 164.5 189.5 214.5 240.0
80 4000 4000 9.5 26.0 45.0 64.0 82.5 101.0 120.0 139.5 161.5 183.5 206.0
90 4500 4500 8.0 22.0 38.5 55.5 72.0 89.0 105.5 122.0 140.0 159.5 179.0
100 5000 5000 7.0 19.0 33.5 49.0 64.0 79.0 94.0 109.0 124.0 140.0 158.0
Table 8.6 Battery Run Time in Minutes Model: GXT5-5000HVRT5UXLN
70 Proprietary and Confidential ©2024 Vertiv Group Corp. 8 Specifications
Vertiv™ Liebert® GXT5 UPS Installer/User Guide

Table of Contents

Other manuals for Vertiv LIEBERT GXT5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv LIEBERT GXT5 Series and is the answer not in the manual?

Vertiv LIEBERT GXT5 Series Specifications

General IconGeneral
ModelLIEBERT GXT5 Series
Product TypeUPS
TopologyDouble Conversion Online
DisplayLCD
Form FactorTower, Rackmount
Output Voltage200/208/220/230/240 VAC
Output Frequency50/60Hz ±0.1Hz (battery mode)
Typical Backup TimeVaries by model and load
Communication PortsUSB, RS-232
Operating Temperature0°C to 40°C (32°F to 104°F)
Relative Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
CertificationsUL, cUL, CE, RoHS
Battery TypeValve Regulated Lead Acid (VRLA)