EasyManua.ls Logo

Vertiv Liebert iCOM CMS - Modbus RTU Setup; Modbus TCP Setup

Vertiv Liebert iCOM CMS
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.4.1 Modbus RTU Set Up
NOTE: The protocol will not work with the control board’s default IP address: 169.254.24.7. Make sure a
Static or DCHP address is set. See Connection Settings on page 25.
External monitoring can be performed via Modbus serial connection.
1. Click > BMS Setup.
The BMS SETUP panel displays.
2. Select Modbus.
The MODBUS panel displays.
3. In the Interface field, select Modbus RTU.
4. Select the Modbus RTU settings, then click Save.
Modbus RTU communication settings
Interface
Selects type of Modbus communication.
Access Level
Selects read-only or read/write access.
Node ID
Modbus node number (1 to 247).
Data Rate
Selects rate of Modbus communication.
Parity
Selects type of communication parity check.
Stop Bits
Selects number of communication stop bits.
3.4.2 Modbus TCP Set Up
External monitoring can be performed via Modbus TCP connection.
NOTE: The protocol will not work with the control board’s default IP address: 169.254.24.7. Make sure a
Static or DCHP address is set. See Connection Settings on page 25.
1. Click > BMS Setup.
The BMS SETUP panel displays.
2. Select Modbus.
The MODBUS panel displays.
3 Service and Advanced Operation
23

Table of Contents

Other manuals for Vertiv Liebert iCOM CMS

Related product manuals