EasyManuals Logo

Vertiv Liebert iCOM CMS User Manual

Vertiv Liebert iCOM CMS
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
3. Based on the information provided by the IT administrator, select the Mode used for IP-address
assignment:
DHCP—automatically assigns the settings from the organization’s network.
Static—requires that you enter a dedicated IP address, subnet mask, default gateway,
and DNS servers.
4. If Static mode is selected, enter the settings obtained from the IT administrator:
IP address
Subnet mask
Gateway
DNS servers
5. Click Save.
4.8 Setting Up BMS serial communication
NOTE: The protocol will not work with the control board’s default IP address: 169.254.24.7. Make sure a
Static or DCHP address is set. See Connection Settings on page 25.
NOTE: For external monitoring via Ethernet connection, see Modbus TCP Set Up on page 23.
To set up the BMS connection:
1. Depending on the type of BMS serial connection:
For Modbus RTU, connect a serial cable to the correct 485 port on the control board (see
Figure 4.1 on page36).
2. On the web UI, click > BMS Setup, select the serial option to use, and configure the
communication settings:
For Modbus serial communication, see Modbus RTU Set Up on page 23.
Vertiv™ | Lieber iCOM CMS™ Intaller/User Guide
42

Table of Contents

Other manuals for Vertiv Liebert iCOM CMS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert iCOM CMS and is the answer not in the manual?

Vertiv Liebert iCOM CMS Specifications

General IconGeneral
BrandVertiv
ModelLiebert iCOM CMS
CategoryControl Systems
LanguageEnglish

Related product manuals