3.6 Backing-up and Restoring settings
iCOMCMS settings may be saved to a local disk or USB drive, and the saved files may exported or
imported to restore iCOMCMS if it is replaced or if a problem occurs. You can import and export
configuration settings to apply the configuration to other units, and you can also return iCOMCMS to
factory-default settings.
3.6.1 Backing-up iCOM CMS settings
Save a copy of the settings in a descriptively named file. Use a back-up file to restore the unit settings in
the event of a failure.
NOTE: Backing-up the iCOMCMS settings does not save settings stored on the cooling unit’s iCOM
display, including setpoints, alarm settings, and sensor calibration. The back-up file also does not save
the cloud-registration status.
1. Click > Settings Management > Backup & Restore.
The BACKUP & RESTORE panel opens.
2. Select the Location to which the backup will be saved.
NOTE: Only a single back-up file may be saved in one location/on one USB drive. Saving to the same
location/drive overwrites the previous file.
3. Click Backup in the lower-right corner, then OK in the confirmation dialog.
The back-up file is saved and a notification indicates that back up is successful.
Remove the USB drive from the port if used.
3.6.2 Restoring iCOMCMS settings
Copy the settings from a back-up file to return iCOMCMS function to what it was before the problem or
failure. The settings may be restored from a file on the local disk or a USB drive.
1. Click > Settings Management > Backup & Restore.
The BACKUP & RESTORE panel opens.
2. Click the Location from which the settings will be restored.
3. Click Restore in the lower-right corner, then OK in the confirmation dialog.
The settings are restored from the file, a notification indicates that restoration is successful,
and the display restarts.
Remove the USB drive from the port if used.
3.6.3 Exporting iCOMCMS settings
Export a copy of the settings to a descriptively named file. Use exported settings to import the
configurations into other units.
NOTE: Exported settings do not include the settings stored on the cooling unit’s iCOM display,
including setpoints, alarm settings, and sensor calibration.
1. Click > Settings Management > Import and Export.
The IMPORT & EXPORT panel opens.
Vertiv™ | Lieber iCOM CMS™ Intaller/User Guide
26

Table of Contents

Other manuals for Vertiv Liebert iCOM CMS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert iCOM CMS and is the answer not in the manual?

Vertiv Liebert iCOM CMS Specifications

General IconGeneral
BrandVertiv
ModelLiebert iCOM CMS
CategoryControl Systems
LanguageEnglish

Related product manuals