Vertiv™ | Liebert® LDMF™ Distribution Monitoring User Manual | 49
6.0 SPECIFICATIONS
ELECTRICAL
Voltage 120 - 240 VAC (-13% to +6%)
Frequency 50 and 60Hz
Current Transformers Rating
(Secondary Winding)
1A for Branch Circuits and Subfeeds
1A for Panelboard Main Breaker
BSM Current 0.5A to 120A
CT Accuracy
5% for 0.5-2A
1% for 2 - 100A
5% for 100-120A
Minimum Current 200mA
ENVIRONMENTAL
Humidity 0-95%
Temperature (Non-Operating) -68°F to 158°F (-20°C to 70°C)
Temperature (Operating) 32°F to 104°F (0°C to 40°C)