1.6
Operating Parameters
In this section, the environmental conditions will be discussed, which includes the Operating
and Storage environment:
1.6.1 Storage Environment
The table 1.2 defines the various storage aspects and requirements, which also includes the
Ambient Humidity, Ambient temperature, and Storage time conditions.
Table 1.2
General Requirements Indoor, clean and without dust
Ambient Humidity < 95% RH
Ambient Temperature
~
Storage Time
Total transportation and storage time should not
exceed six months. Otherwise, the performance needs
to be re-calibrated
1.6.2 Operating Environment
The table 1.3 defines the various requirements and aspects of the Operating environment,
including the Ambient Temperature, Protection Level, Attitude, and the voltage range.
Table 1.3
Item Requirements
Ambient Temperature
Indoor 18° C ~ 35° C
Outdoor
-15° C ~ +45°C, if low temperature kit is used, the
lowest outdoor operating temperature is -34°C.
Protection Level IP20
Altitude
<1000m. If the altitude is above 1000m, then Derating will
occur. Please contact Vertiv™ for this resolution
Operating Voltage range
380~415 (-10%~+6%)V,3N~50/60Hz