50 Use in Hazardous Environments WAGO-I/O-SYSTEM 750
750-461 2AI Pt100/RTD
Manual
Version 1.4.1
Pos: 36.16 /Serie 750 (W AGO-I/O-SYSTEM)/Einsatz in Ex-Bereichen/Bei spielbedruckung und Textdetail CEC_2017 @ 29\mod_14 97865583297_21.doc x @ 424736 @ @ 1
Figure 20: Text DetailMarking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 38: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking
Description
Dust
Ex
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use
Gases
Ex
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 0
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use
Pos: 36.17 /Dokumenta tion allgemein/Glie derungselemente/---Sei tenwechsel--- @ 3\mod_122110804507 8_0.docx @ 21810 @ @ 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO 750-461 Series and is the answer not in the manual?

WAGO 750-461 Series Specifications

General IconGeneral
BrandWAGO
Model750-461 Series
CategoryControl Unit
LanguageEnglish

Related product manuals