WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 51
750-461 2AI Pt100/RTD
Manual
Version 1.4.1
Pos: 36.18 /Alle Seri en (Allgemeine Module)/ Überschriften/Eben e 2/Errichtungsbes timmungen - Überschr ift 2 @ 3\mod_1232453624234 _21.docx @ 26370 @ 2 @ 1
7.2 Installation Regulations
Pos: 36.19 /Alle Seri en (Allgemeine Module)/ Einsatz in Ex-Bereic hen/Errichtungsbes timmungen Einleitung_20 13 @ 14\mod_1360582328 318_21.docx @ 111371 @ @ 1
For the installation and operation of electrical equipment in hazardous areas, the
valid national and international rules and regulations which are applicable at the
installation location must be carefully followed.
Pos: 36.20 /Dokumenta tion allgemein/Glie derungselemente/----Leer zeile-(1Z) ---- @ 28\mod_1485262995837_0. docx @ 404006 @ @ 1
Pos: 36.21.1 /Alle Ser ien (Allgemeine Module) /Überschriften/ Ebene 3/Besondere Hin weise hinsichtlic h Explosionsschutz - Über schrift 3 @ 29\mod_14915584098 38_21.docx @ 415454 @ 3 @ 1
7.2.1 Special Notes Regarding Explosion Protection
Pos: 36.21.2 /Seri e 750 (WAGO-I/O-SYSTEM)/Einsatz in E x-Bereichen/Besondere Hin weise hinsichtlic h Explosionsschutz_ 2017 @ 29\mod_1491556994025_ 21.docx @ 415448 @ @ 1
The following warning notices are to be posted in the immediately proximity of the
WAGO-I/O-SYSTEM 750 (hereinafter “product”):
WARNING – DO NOT REMOVE OR REPLACE FUSED WHILE ENERGIZED!
WARNING – DO NOT DISCONNECT WHILE ENERGIZED!
WARNING – ONLY DISCONNECT IN A NON-HAZARDOUS AREA!
Before using the components, check whether the intended application is
permitted in accordance with the respective printing. Pay attention to any
changes to the printing when replacing components.
The product is an open system. As such, the product must only be installed in
appropriate enclosures or electrical operation rooms to which the following
applies:
• Can only be opened using a tool or key
• Inside pollution degree 1 or 2
• In operation, internal air temperature within the range of 0 °C ≤ Ta ≤ +55 °C
or −20 °C ≤ Ta ≤ +60 °C for components with extension number …/025-xxx
or −40 °C ≤ Ta ≤ +70 °C for components with extension number …/040-xxx
• Minimum degree of protection: min. IP54 (acc. to EN/IEC 60529)
• For use in Zone 2 (Gc), compliance with the applicable requirements of the
standards EN/IEC/ABNT NBR IEC 60079-0, -7, -11, -15
• For use in Zone 22 (Dc), compliance with the applicable requirements of
the standards EN/IEC/ABNT NBR IEC 60079-0, -7, -11, -15 and -31
• For use in mining (Mb), minimum degree of protection IP64 (acc. EN/IEC
60529) and adequate protection acc. EN/IEC/ABNT NBR IEC 60079-0 and
-1
• Depending on zoning and device category, correct installation and
compliance with requirements must be assessed and certified by a “Notified
Body” (ExNB) if necessary!