EasyManua.ls Logo

WAGO SYSTEM 750 - Technical Data; Dimensions and Weight; Voltage Supply; Measuring Inputs

WAGO SYSTEM 750
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WAGO-I/O-SYSTEM 750 Device Description 21
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
Pos: 44 /Dokum entat ion all gemei n/Gli eder ungsel eme nte/---Seit en wechs el--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Pos: 45 /Al l e Ser ien (Al lg emei ne M od ule)/Ü b ersc hrif te n für all e S eri en/G erä teb esc hreib ung /Te ch nisc he D ate n - Ü ber schri ft 2 @ 3\ mod_1232967587687_21.docx @ 26924 @ 2 @ 1
3.6 Technical Data
Pos: 46.1 /Serie 750 (WAGO-I/O-SYST EM) /Ger äte besc hrei bu ng/T echni sc he Da te n/A nal ogeing ang s kle mme n/Tec hnis ch e D aten 75 0-0 493 @ 13\ mod_1348667756744_21.doc x @ 103558 @ 33333 @ 1
3.6.1 Dimensions and Weight
Table 7: Technical Data ‒ Dimensions and Weight
Width
12 mm
Height (from upper edge of carrier rail)
64 mm
Length
100 mm
Weight
48 g
3.6.2 Voltage Supply
Table 8: Technical Data ‒ Voltage Supply
Voltage
System voltage DC 5 V
(via internal bus)
Current consumption
100 mA
Category of overvoltage
III
Rated voltage impulse
4 kV
Degree of distortion
2
3.6.3 Measuring Inputs
Table 9: Technical Data Measuring Inputs
Number of inputs
6 (3 voltage inputs, 3 current inputs)
Rated measuring voltage max.
Input resistance typ.
Phase-to-phase voltage Lx - Ly:
480 VAC
Phase voltage Lx - N: 277 VAC/DC
1072 kΩ
Measuring current max.
1 A for 750-493,
5 A for 750-493/000-001
1 A for 750-493,025-000
5 A for 750-493/025-001
Input resistance typ.
22 mΩ for 750-493,
5 mΩ for 750-493/000-001
22 mΩ for 750-493/025-000
5 mΩ for 750-493/025-001
Frequency range
- DC filter activated
- DC filter deactivated
10 … 2000 Hz
0 … 2000 Hz
Max. frequency
7.2 kHz
Signal form
any (in consideration of the frequency
range and max. frequency)

Table of Contents

Related product manuals