50 Connect Devices WAGO-I/O-SYSTEM 750
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
Pos: 75 /Al l e Ser ien (Al lg emei ne M od ule)/Ü b ersc hrif te n für all e S eri en/A nsc hließ e n/Ger ät e ans chl ieß en - Ü ber sc hrift 1 @ 3\ mod_1234172889468_21.docx @ 27460 @ 1 @ 1
7 Connect Devices
Pos: 76 /S eri e 7 50 ( WA GO-I/O- SYST EM) /Ans chl i eßen/ Lei ter an C AG E C LAM P ans chl ieß en ( all ge mein) - Üb ersc hrift 2 u nd Text @ 3\mod_1225448660171_21.docx @ 24928 @ 2 @ 1
7.1 Connecting a Conductor to the CAGE CLAMP
®
The WAGO CAGE CLAMP
®
connection is appropriate for solid, stranded and
finely stranded conductors.
Only connect one conductor to each CAGE CLAMP
®
!
Only one conductor may be connected to each CAGE CLAMP
®
.
Do not connect more than one conductor at one single connection!
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
Exception:
If it is unavoidable to jointly connect 2 conductors, then you must use a ferrule to
join the wires together. The following ferrules can be used:
Length: 8 mm
Nominal cross section
max.
: 1 mm
2
for 2 conductors with 0.5 mm
2
each
WAGO product: 216-103 or products with comparable properties
1. For opening the CAGE CLAMP
®
insert the actuating tool into the opening
above the connection.
2. Insert the conductor into the corresponding connection opening.
3. For closing the CAGE CLAMP
®
simply remove the tool. The conductor is
now clamped firmly in place.
Figure 11: Connecting a Conductor to a CAGE CLAMP
®
Pos: 77 /Dokum entat ion all gemei n/Gli eder ungsel eme nte/---Seit en wechs el--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1