4 Process Image
Pos: 67 /S eri e 7 50 ( WA GO-I/O- SYST EM) /Pr oz ess abbil d Kl e mmen bus /An alog eing ang s klem men /Pr ozes sab bild 750- 0493 @ 5\mod_1251702231515_21.docx @ 41084 @ 2222 @ 1
The 750-493 I/O module provides, on 3 logical channels, a maximum of 9 bytes
input and 9 bytes output process data to a fieldbus coupler/controller. The data to
be sent and received will be stored in up to 6 input and output bytes (D0 ... D5),
i.e. in 3 data words. This means 3 process data are sent.
3 control bytes (C0 ... C2) and 3 status bytes (S0 … S2) are used for selecting
process data and for setting parameters.
Notice that the process data image depends on the used fieldbus coupler/
controller!
Mapping the process data into the process image is specific for the fieldbus
coupler/controller used. You will find both this information and the specific
configuration of the relevant control/status bytes in the manual of the
coupler/controller, section "Fieldbus Specific Configuration of Process Data"
which describes the process image.