EasyManua.ls Logo

WAGO SYSTEM 750 - 4 Process Image; Input and Output Data; Table 15: Input and Output Data

WAGO SYSTEM 750
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 Process Image WAGO-I/O-SYSTEM 750
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
Pos: 66 /Al l e Ser ien (Al lg emei ne M od ule)/Ü b ersc hrif te n für all e S eri en/ __ n och ni cht ei ns ortier te Ü b ersc hrif te n m üssen noc h eins orti ert wer den __/ Proz ess a bbil d - Ü bersc hri ft 1 @ 4\mod_1240983067828_21.docx @ 31942 @ 1 @ 1
4 Process Image
Pos: 67 /S eri e 7 50 ( WA GO-I/O- SYST EM) /Pr oz ess abbil d Kl e mmen bus /An alog eing ang s klem men /Pr ozes sab bild 750- 0493 @ 5\mod_1251702231515_21.docx @ 41084 @ 2222 @ 1
The 750-493 I/O module provides, on 3 logical channels, a maximum of 9 bytes
input and 9 bytes output process data to a fieldbus coupler/controller. The data to
be sent and received will be stored in up to 6 input and output bytes (D0 ... D5),
i.e. in 3 data words. This means 3 process data are sent.
3 control bytes (C0 ... C2) and 3 status bytes (S0 … S2) are used for selecting
process data and for setting parameters.
Notice that the process data image depends on the used fieldbus coupler/
controller!
Mapping the process data into the process image is specific for the fieldbus
coupler/controller used. You will find both this information and the specific
configuration of the relevant control/status bytes in the manual of the
coupler/controller, section "Fieldbus Specific Configuration of Process Data"
which describes the process image.
4.1 Input and Output Data
Table 15: Input and Output Data
9 Bytes Input Data
9 Bytes Output Data
S0
Status byte 0
C0
Control byte 0
D0
Input data word 1 (LSB)
D0
Output data word 1 (LSB)
D1
Input data word 1 (MSB)
D1
Output data word 1 (MSB)
S1
Status byte 1
C1
Control byte 1
D2
Input data word 2 (LSB)
D2
Output data word 2 (LSB)
D3
Input data word 2 (MSB)
D3
Output data word 2 (MSB)
S2
Status byte 2
C2
Control byte 2
D4
Input data word 3 (LSB)
D4
Output data word 3 (LSB)
D5
Input data word 3 (MSB)
D5
Output data word 3 (MSB)