EasyManua.ls Logo

WAGO SYSTEM 750 - Table 19: Control Byte C1

WAGO SYSTEM 750
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WAGO-I/O-SYSTEM 750 Process Image 31
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
Table 19: Control Byte C1
Control Byte C1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg_Com
Reserved
Channel_ID
ProcDat_ID
ProcDat_
ID
Here, enter the process data index for the physical variable you wish to read out
using input data word 2.
0:
Current (rms)
1:
Voltage (rms)
2:
Active power
3:
Power factor
4:
Active energy
5:
Max. current
6:
Max. voltage
7:
Max. active power
8:
Frequency
9:
Min. current
10:
Min. voltage
11:
Min. active power
12 .... 15:
Reserved
Channel_
ID
Simple
process
image
Always 0
(With the simple process image the channel index has no significance.)
Flexible
process
image
Here, enter the channel index for the channel from which you wish to
read out a measured value using input data word 2.
0:
Channel 1
1:
Channel 2
2:
Channel 3
3:
Calibration mode active
Reg_Com
0:
Process data communication
1:
Register communication

Table of Contents

Related product manuals